Power and cooling
Power and Cooling Density2.0 – 4.0 kVA per cabinet
Utility Feeders2
UPS Configuration2N
UPS Redundancy2N
Standby Power Configuration8 x 1,375 kVA and 3 x 2,000 kVA diesel generators
Standby Power RedundancyN+1
Cooling ConfigurationCRAC units and water-cooled centrifugal chillers
Cooling RedundancyN+1 (on chillers) and N+25% (on CRAC units)
Cooling Density

• 90 watts per sq ft

• Upgradable cooling density

Edit Content
Security
PhysicalMan trap entry
Human24/7 on-site security officers
ElectronicBiometric readers (in common areas), additional biometric readers (optional), PIN & card readers, CCTV and recorders, motion detection
Edit Content
AMENITIES
Break Room
Work Kiosks
Loaner Tools
Wifi
Showers
Conference Room
Crash Carts
Edit Content
RACK INFORMATION
Rack Type42U Smart rack
Size600mm x 1200mm / 600mm x 1100mm
Lock3-digits combination lock (front and rear door for Colocatopn Rack)
Power PlugC13-C14 & C19-C20 Power outlet combination
Intelligent Power Distribution Unit (IPDU)2 x 32A Commando plug IPDU with 2 breakers
PDU

• 2N PDU

• 2 x Primary circuit

• Three-phase circuit breaker with hot-swappable breaker module

Edit Content
CONNECTIVITY
Carrier-neutral with Dual incoming
Peered with multiple Tier I Network providers
Dual riser power or data routing
Border Gateway Protocol (BGP)
FREE Anti-DDoS Protection up to 5Gbps
Over 20 Internet Service Providers
Space
Colocation Space12,610sqft each floor
Office Space7,000 sq ft each floor
Building Type
Features

• Double-layer brick with cavity insulation wall construction

• Double-layer concrete roof slab to prevent water leakage

Type4-story, purposed built Data Centre Building and office block with an interconnecting link bridge
Passenger Lift1,020kg lift – 900mm(W) x 1550mm(D) x 2100mm(H)
Goods Lift1,905kg lift – 1550mm(W) x 2600mm(D) x 2600mm(H)
ParkingAdjacent to the building (free)
Meters above sea levelStanding tall 24m above sea level
Floor
Floor TypeRaised at 800mm, Slab height at 4,500mm
Floor Load CapacityData Center for 10kN/M2, Facility area for 15kN/M2
Fire Detection

• Highly sensitive smoke detector (HSSD)

• Available above and below the raised floor

• Addressable heat and smoke detectors

Fire Suppression

• Pre-action water mist within the data center and common area

• (Optional) FM-200 Gas Suppression System

• hand-held CO2 fire extinguisher

Green By Design
LEED Rating SystemGold (Phase IX)
Green Building Rating SystemBCA-IMDA Green Mark Award (Certified)
TemperatureGranular temperature monitoring and cold aisle containment
Temperature Control24 Degree Celsius (°C), +/-2(°C)
Humidity Control50% RH +/- 10%
LightingOptimized lighting controls
Renewable Energy100% biomass International Renewable Energy Certificates (IRECs) in 2016
Power and cooling
Power and Cooling Density2.0 – 4.0 kVA per cabinet
Utility Feeders2
UPS Configuration2N
UPS Redundancy2N
Standby Power Configuration8 x 1,375 kVA and 3 x 2,000 kVA diesel generators
Standby Power RedundancyN+1
Cooling ConfigurationCRAC units and water-cooled centrifugal chillers
Cooling RedundancyN+1 (on chillers) and N+25% (on CRAC units)
Cooling Density

• 90 watts per sq ft

• Upgradable cooling density

Security
PhysicalMan trap entry
Human24/7 on-site security officers
ElectronicBiometric readers (in common areas), additional biometric readers (optional), PIN & card readers, CCTV and recorders, motion detection
AMENITIES
Break Room
Work Kiosks
Loaner Tools
Wifi
Showers
Conference Room
Crash Carts
RACK INFORMATION
Rack Type42U Smart rack
Size600mm x 1200mm / 600mm x 1100mm
Lock3-digits combination lock (front and rear door for Colocatopn Rack)
Power PlugC13-C14 & C19-C20 Power outlet combination
Intelligent Power Distribution Unit (IPDU)2 x 32A Commando plug IPDU with 2 breakers
PDU

• 2N PDU

• 2 x Primary circuit

• Three-phase circuit breaker with hot-swappable breaker module

CONNECTIVITY
Carrier-neutral with Dual incoming
Peered with multiple Tier I Network providers
Dual riser power or data routing
Border Gateway Protocol (BGP)
FREE Anti-DDoS Protection up to 5Gbps
Over 20 Internet Service Providers
Space
Colocation Space 12,610sqft each floor
Office Space 7,000 sq ft each floor
Building Type
Features Double layer concrete roof slab, double layer brick with cavity insulation wall construction
Type 4-story, purposed built Data Centre Building and office block with an interconnecting link bridge
Parking Adjacent to the building (free)
Meters above sea level Standing tall 24m above sea level
Floor
Floor Type Raised at 800mm, Slab height at 4,500mm
Floor Load Capacity Data Center for 10kN/M2, Facility area for 15kN/M2
Fire Detection Highly sensitive smoke detector (HSSD) available above and below the raised floor, addressable heat and smoke detectors
Fire Suppression Pre-action water mist within the data center and common area, FM-200 Gas Suppression System, hand-held CO2 fire extinguisher
Green By Design
LEED Rating System Gold (Phase IX)
Green Building Rating System BCA-IMDA Green Mark Award (Certified)
Temperature Granular temperature monitoring and cold aisle containment
Lighting Optimized lighting controls
Renewable Energy 100% biomass International Renewable Energy Certificates (IRECs) in 2016
Power and cooling
Power and Cooling Density2.0 – 4.0 kVA per cabinet
Utility Feeders2
UPS Configuration2N
UPS Redundancy2N
Standby Power Configuration8 x 1,375 kVA and 3 x 2,000 kVA diesel generators
Standby Power RedundancyN+1
Cooling ConfigurationCRAC units and water-cooled centrifugal chillers
Cooling RedundancyN+1 (on chillers) and N+25% (on CRAC units)
Security
PhysicalMan trap entry
Human24/7 on-site security officers
ElectronicBiometric readers (in common areas), additional biometric readers (optional), PIN & card readers, CCTV and recorders, motion detection
AMENITIES
Break Room
Work Kiosks
Loaner Tools
Wifi
Showers
Conference Room
Crash Carts
RACK INFORMATION
Rack Type42U Smart rack
Size600mm x 1200mm
Lock3-digits combination lock (front and rear door)
Power PlugC13-C14 & C19-C20 Power outlet combination
Intelligent Power Distribution Unit (IPDU)2 x 32A Commando plug IPDU with 2 breakers
CONNECTIVITY
Carrier-neutral with Dual incoming
Peered with multiple Tier I Network providers
Dual riser power or data routing
Border Gateway Protocol (BGP)
FREE Anti-DDoS Protection up to 5Gbps
Over 20 Internet Service Providers
Building
Space
Colocation Space12,610sqft each floor
Office Space7,000 sq ft each floor
Building Type
FeaturesDouble layer concrete roof slab, double layer brick with cavity insulation wall construction
Type4-story, purposed built Data Centre Building and office block with an interconnecting link bridge
ParkingAdjacent to the building (free)
Meters above sea levelStanding tall 24m above sea level
Floor
Floor TypeRaised at 800mm, Slab height at 4,500mm
Floor Load CapacityData Center for 10kN/M2, Facility area for 15kN/M2
Fire DetectionHighly sensitive smoke detector (HSSD) available above and below the raised floor, addressable heat and smoke detectors
Fire SuppressionPre-action water mist within the data center and common area, FM-200 Gas Suppression System, hand-held CO2 fire extinguisher
Facilities
Power
Incoming PowerDual 11KV with 5MVA capacity power feed from different power grids and substations.
Power Path Different incoming cabling routes for redundancy. Redundant room for TNB, Generator, Main Switch Room, UPS room and etc.
UPS Configuration2N4 sets of 3 x 400KVA UPS with N+1 configuration with 10 minutes backup time under full load.
UPS Redundancy2N
Power Distribution Unit (PDU)2N PDU, 2x primary circuit, 3-phase circuit breaker with hot-swappable
Standby Power Configurationx 2MVA diesel generators (expandable to 8MVA) running up to 48 hours or 4 sets of Power Generators with N+1 configuration with 24 hours of backup diesel capacity
Standby Power RedundancyN+1
Cooling ConfigurationCRAC units and water-cooled centrifugal chillers
Cooling
SystemCold Aisle Containment System
Cooling Density90 watts per sqft, upgradable cooling density
Cooling ConfigurationN+1 with dual power supply for each CRAC unit, and Down Flow Precision Air Conditioners
Cooling RedundancyN+1 CRAC Unit
Additional Efforts
Temperature Control24 degree Celcius, 1/-2 celcius
Humidity Control50% RH 1/-10%
Transformer4x 3MVA cast resin dry-type transformers
SECURITY
PhysicalMan trap entry, Perimeter Fencing
Human24/7 on-site management and security officers
ElectronicAccess card control system at all entrances and exits, CCTV surveillance
AMENITIES
MDF Room
Loading Bay
Server Room
Break Room
UPS Battery Storage Room (with hydrogen gas sensor)
Wifi
RACK INFORMATION
Rack Type42U Smart rack
Size600mm x 1200mm
Lock3-digits combination lock (front and rear door)
Power PlugC13-C14 & C19-C20 Power outlet combination
Intelligent Power Distribution Unit (IPDU)2 x 32A Commando plug IPDU with 2 breakers
GREEN BY DESIGN
Green Building Index (GBI) Certified
CONNECTIVITY
Carrier-neutral with Dual incoming
Peered with multiple Tier I Network providers
Dual riser power or data routing
Border Gateway Protocol (BGP)
FREE Anti-DDoS Protection up to 5Gbps
Over 20 Internet Service Providers

Join us for SembangDR Day!

Let’s sembang about disaster recovery (DR), connect with industry peers, and see how fast we restore services after a disaster.

Date: May 16th, 2024 (Thursday)
Time: 2:00pm – 5:30pm
Venue: Idea Zone, IMAZIUM, Damansara Uptown

Nullam quis risus eget urna mollis ornare vel eu leo. Aenean lacinia bibendum nulla sed 

Sign up for web hosting today!

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.